E-6
A p p e n d i x E : T e c h n i c a l S p e c i f i c a t i o n s
AC890PX AC Drive
Electrical Ratings (380-460V)
Units
890
P
X
/4
/0
215/
890
P
X
/4
/0
260/
890
P
X
/4
/0
300/
890
P
X
/4
/0
420/
890
P
X
/4
/0
480/
890
P
X
/4
/0
520/
890
P
X
/4
/0
580/
Maximum Prospective Short Circuit Current
kA
65
65
65
65
65
65
65
Nominal Input Voltage
(note 2)
V
400
400
400
400
400
400
400
Motor Power
kW
110
132
160
200
250
280
315
Output Current
(note 4)
A
215
260
300
420
480
520
580
AC Input Current
(notes 1 & 2)
A
194
222
270
340
423
475
534
Drive Total Power Loss
W
2730
3243
3790
4958
5784
6131
6306
Maximum Switching Frequency
(note 3)
kHz
2
2
2
2
2
2
2
Euro
pe
Input Bridge I
2
t
A
2
s
245000
245000
245000
1330000
1330000
1330000
1330000
Nominal Input Voltage
(note 2)
V
460
460
460
460
460
-
460
Motor Power
Hp
150
200
250
300
400
-
500
Output Current
(note 4)
A
200
250
300
380
460
-
580
AC Input Current
(notes 1 & 2)
A
171
218
272
329
436
-
549
Drive Total Power Loss
W
2557
3166
3817
4591
5716
-
6582
Maximum Switching Frequency
(note 3)
kHz
2
2
2
2
2
-
2
HEAV
Y D
U
T
Y
US
A/C
an
ad
a
Input Bridge I
2
t
A
2
s
235000
235000
235000
1200000
1200000
-
1200000
Nominal Input Voltage
(note 2)
V
400
400
400
400
400
400
400
Motor Power
kW
132
160
200
250
315
355
400
Output Current
(note 4)
A
260
340
390
480
600
660
720
AC Input Current
(notes 1 & 2)
A
228
268
336
423
532
602
679
Drive Total Power Loss
W
3230
4120
4877
5783
7378
7997
8950
Maximum Switching Frequency
(note 3)
kHz
2
2
2
2
2
2
2
Euro
pe
Input Bridge I
2
t
A
2
s
245000
245000
245000
1330000
1330000
1330000
1330000
Nominal Input Voltage
(note 2)
V
460
460
460
460
460
-
460
Motor Power
Hp
200
250
300
400
500
-
600
Output Current
(note 4)
A
250
320
380
480
590
-
700
AC Input Current
(notes 1 & 2)
A
222
242
326
436
547
-
659
Drive Total Power Loss
W
3148
3870
4771
5879
7417
-
8894
Maximum Switching Frequency
(note 3)
kHz
2
2
2
2
2
-
2
NO
RM
AL D
U
TY
US
A/C
an
ad
a
Input Bridge I
2
t
A
2
s
235000
235000
235000
1200000
1200000
-
1200000
Summary of Contents for AC890PX Series
Page 8: ......
Page 12: ...1 4 C h a p t e r 1 G e t t i n g S t a r t e d AC890PX AC Drive...
Page 17: ...C h a p t e r 2 P r o d u c t O v e r v i e w 2 5 AC890PX AC Drive 890PX bottom wire entry...
Page 22: ...2 10 C h a p t e r 2 P r o d u c t O v e r v i e w AC890PX AC Drive...
Page 74: ...4 8 C h a p t e r 4 A s s o c i a t e d E q u i p m e n t AC890PX AC Drive...
Page 96: ...5 22 C h a p t e r 5 O p e r a t i n g t h e D r i v e AC890PX AC Drive...
Page 162: ...8 22 C h a p t e r 8 T r i p s F a u l t F i n d i n g AC890PX AC Drive...
Page 170: ...9 8 C h a p t e r 9 R o u t i n e M a i n t e n a n c e R e p a i r AC890PX AC Drive...
Page 286: ...D 84 A p p e n d i x D P r o g r a m m i n g AC890PX AC Drive Functional Description...