D-44
A p p e n d i x D : P r o g r a m m i n g
AC890PX AC Drive
FEEDBACKS
SETUP::MOTOR CONTROL::FEEDBACKS
Designed for all Motor Control Modes.
The FEEDBACKS block allows you to view speed feedback and motor current related diagnostics.
Parameter Descriptions
QUADRATIC TORQUE
PREF: 70.01
Default: FALSE
Range: FALSE/TRUE
Designed for all Motor Control Modes.
When TRUE, selects QUADRATIC allowing higher continuous ratings with less overload capability. Quadratic Torque operation is especially
suited to fan or pump applications. When FALSE, selects CONSTANT duty.
OVERLOAD LEVEL
PREF: 70.20
Default: HIGH
Range: See below
Designed for all Motor Control Modes, except PMAC control mode.
This reduces I*t limit for shaftless printing applications. However, with OVERLOAD LEVEL set to LOW, no pwm frequency reduction occurs
during overload conditions.
Enumerated Value : Level
0 : LOW
130% for 60s : sets the I*t limit
1 : HIGH
150% for 60s : sets the I*t limit
DC LINK VOLTS
PREF: 70.02
Default: —. V
Range: —. V
This shows the voltage across the dc link capacitors.
TERMINAL VOLTS
PREF: 70.03
Default: —. V
Range: —. V
This shows the rms voltage, between phases, applied by the Drive to the motor terminals.
Summary of Contents for AC890PX Series
Page 8: ......
Page 12: ...1 4 C h a p t e r 1 G e t t i n g S t a r t e d AC890PX AC Drive...
Page 17: ...C h a p t e r 2 P r o d u c t O v e r v i e w 2 5 AC890PX AC Drive 890PX bottom wire entry...
Page 22: ...2 10 C h a p t e r 2 P r o d u c t O v e r v i e w AC890PX AC Drive...
Page 74: ...4 8 C h a p t e r 4 A s s o c i a t e d E q u i p m e n t AC890PX AC Drive...
Page 96: ...5 22 C h a p t e r 5 O p e r a t i n g t h e D r i v e AC890PX AC Drive...
Page 162: ...8 22 C h a p t e r 8 T r i p s F a u l t F i n d i n g AC890PX AC Drive...
Page 170: ...9 8 C h a p t e r 9 R o u t i n e M a i n t e n a n c e R e p a i r AC890PX AC Drive...
Page 286: ...D 84 A p p e n d i x D P r o g r a m m i n g AC890PX AC Drive Functional Description...