A p p e n d i x C : C e r t i f i c a t i o n
C-13
AC890PX AC Drive
EMC Immunity Levels
Port
Phenomenon
Basic standard
for test method
Level
Performance
(acceptance criterion)
ESD
IEC 61000-4-2
4 kV CD or 8 kV AD
if CD impossible
B
Enclosure port
Radio-frequency electromagnetic field, amplitude
modulated.
IEC 61000-4-3
see also 5.3.4
80 MHz to 1000 Mhz
10 V/m
80% AM (1 kHz)
A
Fast transient-burst
IEC 61000-4-4
2 kV/5 kHz
a
B
Surge
b
1,2/50 µs, 8/20 µs
IEC 61000-4-5
1 kV
c
2 kV
d
B
Power ports
Conducted radio-frequency common mode
e
IEC
61000-4-6
see also 5.3.4
0,15 MHz to 80 MHz
10 V
80 % AM (1 kHz)
A
Power interfaces
Fast transient-burst
e
IEC 61000-4-4
2 kV/5 kHz
Capacitive clamp
B
Fast transient-burst
e
IEC 61000-4-4
1 kV/5 kHz
Capacitive clamp
B
Signal interfaces
Conducted radio-frequency common mode
e
IEC
61000-4-6
see also 5.3.4
0,15 MHz to 80 MHz
10 V
80 % AM (1 kHz)
A
Fast transient-burst
e
IEC 61000-4-4
2 kV/5 kHz
Capacitive clamp
B
Surge
f
1,2/50 µs, 8/20 µs
IEC 61000-4-5
1 kV
d,f
B
Ports for process
measurement
control lines
Conducted radio-frequency common mode
e
IEC
61000-4-6
see also 5.3.4
0,15 MHz to 80 MHz
10 V
80 % AM (1 kHz)
A
CD : contact discharge
AD : air discharge AM : amplitude modulation
a
Power ports with current rating < 100 A: direct coupling using the coupling and decoupling network. Power ports with current rating
≥
100 A: direct coupling
or capacitive clamp without decoupling network. If the capacitive clamp is used, the test level shall be 4 kV/2,5 kHz.
b
Applicable only to power ports with current consumption , 63 A during light load test conditions as specified in 5.1.3. The rated impulse voltage of the basic
insulation shall not be exceeded (see IEC 60664-1).
c
Coupling line-to-line.
d
Coupling line-to-earth.
e
Applicable only to ports or interfaces with cables whose total length according to the manufacturer's functional specification may exceed 3 m.
f
Applicable only to ports with cables whose total length according to the manufacturer's functional specification may exceed 30 m. In the case of a shielded
cable, a direct coupling to the shield is applied. This immunity requirement does not apply to fieldbus or other signal interfaces where the use of surge
protection devices is not practical for technical reasons. The test is not required where normal functioning cannot be achieved because of the impact of the
coupling/decoupling network on the equipment under test (EUT).
Minimum immunity requirements for PDSs intended for use in the second environment
Summary of Contents for AC890PX Series
Page 8: ......
Page 12: ...1 4 C h a p t e r 1 G e t t i n g S t a r t e d AC890PX AC Drive...
Page 17: ...C h a p t e r 2 P r o d u c t O v e r v i e w 2 5 AC890PX AC Drive 890PX bottom wire entry...
Page 22: ...2 10 C h a p t e r 2 P r o d u c t O v e r v i e w AC890PX AC Drive...
Page 74: ...4 8 C h a p t e r 4 A s s o c i a t e d E q u i p m e n t AC890PX AC Drive...
Page 96: ...5 22 C h a p t e r 5 O p e r a t i n g t h e D r i v e AC890PX AC Drive...
Page 162: ...8 22 C h a p t e r 8 T r i p s F a u l t F i n d i n g AC890PX AC Drive...
Page 170: ...9 8 C h a p t e r 9 R o u t i n e M a i n t e n a n c e R e p a i r AC890PX AC Drive...
Page 286: ...D 84 A p p e n d i x D P r o g r a m m i n g AC890PX AC Drive Functional Description...