CONTACTOR CLOSED
PREF: 92.05
Default: TRUE
Range: FALSE / TRUE
Feedback used to indicate that the external contactor has been closed. It must be TRUE for the sequencer to proceed from the SWITCHED ON
state to the READY STATE, refer to SEQUENCER STATE.
DRIVE ENABLE
PREF: 92.06
Default: TRUE
Range: FALSE / TRUE
This provides a means of electronically inhibiting Drive operation. Whilst running, setting this parameter to FALSE disables the Drive operation and
causes the motor to coast.
NOT FAST STOP
PREF: 92.07
Default: TRUE
Range: FALSE / TRUE
Whilst running or jogging, setting this parameter to FALSE causes the Drive to ramp to zero. The rate is set by FAST STOP RATE in the STOP
function block. The action of setting NOT FAST STOP to TRUE is latched. The Drive cannot be restarted until fast stop is completed.
NOT COAST STOP
PREF: 92.08
Default: TRUE
Range: FALSE / TRUE
Setting this parameter to FALSE disables the Drive operation and causes the motor to coast. The action of setting this parameter to TRUE is latched.
The Drive can not be restarted until the coast stop is completed.
A detailed description of the sequencer states, as indicated by the SEQUENCER STATE parameter, is described in Appendix B.
REMOTE REVERSE
PREF: 92.09
Default: FALSE
Range: FALSE / TRUE
For remote setpoints, setting this parameter TRUE inverts the demanded direction of motor rotation.
REM TRIP RESET
PREF: 92.10
Default: FALSE
Range: FALSE / TRUE
On a transition to TRUE, this input clears latched trips.
TRIP RST BY RUN
PREF: 92.11
Default: TRUE
Range: FALSE / TRUE
This allows the rising edge of run command to clear latched trips.
POWER UP START
PREF: 92.12
Default: FALSE
Range: FALSE / TRUE
If TRUE, this allows the Drive to go directly to run mode on power-up if in remote and a run command is present. If FALSE, a low to high
transition of the run command is required.
TRIPPED
PREF: 92.13
Default: FALSE
Range: FALSE / TRUE
Indicates that there is a latched trip present.
RUNNING
PREF: 92.14
Default: FALSE
Range: FALSE / TRUE
Indicates that that the Drive is in the enabled state.
Summary of Contents for AC890PX Series
Page 8: ......
Page 12: ...1 4 C h a p t e r 1 G e t t i n g S t a r t e d AC890PX AC Drive...
Page 17: ...C h a p t e r 2 P r o d u c t O v e r v i e w 2 5 AC890PX AC Drive 890PX bottom wire entry...
Page 22: ...2 10 C h a p t e r 2 P r o d u c t O v e r v i e w AC890PX AC Drive...
Page 74: ...4 8 C h a p t e r 4 A s s o c i a t e d E q u i p m e n t AC890PX AC Drive...
Page 96: ...5 22 C h a p t e r 5 O p e r a t i n g t h e D r i v e AC890PX AC Drive...
Page 162: ...8 22 C h a p t e r 8 T r i p s F a u l t F i n d i n g AC890PX AC Drive...
Page 170: ...9 8 C h a p t e r 9 R o u t i n e M a i n t e n a n c e R e p a i r AC890PX AC Drive...
Page 286: ...D 84 A p p e n d i x D P r o g r a m m i n g AC890PX AC Drive Functional Description...