A p p e n d i x E : T e c h n i c a l S p e c i f i c a t i o n s
E-11
AC890PX AC Drive
Earthing/Safety Details
Earthing
Each unit must be permanently earthed according to EN 61800-5.
For permanent earthing, EN 61800-5 states that:
A cross-section conductor of at least 10mm² for copper or 16mm
2
aluminium is required.
Use a copper protective earth conductor of at least 10mm² minimum cross-section.
Conductors must be sized in accordance with Local Wiring Regulations which always take precedence.
As a guide, refer to the Input Current for the drive given in the Electrical Ratings tables.
Input Supply Details
(TN) and (IT)
Drives without filters are suitable for earth referenced (TN) or non-earth referenced (IT) supplies.
External filters are available for use on earth referenced (TN) supplies only.
Earth Leakage Current
>>100mA (all models)