D-74
A p p e n d i x D : P r o g r a m m i n g
AC890PX AC Drive
Current
MOT CURRENT PCNT
s
MOT CURRENT RAMP
To start the STANDARD polarisation:
1.
The motor must be stationary, with no load attached to the motor shaft. In this method, there will be a maximum movement of half an
electrical turn of the motor shaft.
2.
Choose a MOTOR PHASE: U, V or M.
3.
Set the current level to apply in the MOT CURRENT PCNT parameter.
4.
Set a ramp value for the current level in the MOT CURRENT RAMP parameter.
5.
Set POLARISATION = ENABLE, POLAR START = FALSE.
6.
Verify that ELEC POS OFFSET is set to 0.0.
7.
Set POLAR START = TRUE.
8.
Apply a torque to the motor and read the value of the ELEC POS parameter.
9.
Stop the motor. Verify that the value of ELEC POS after polarisation matches the theoretical position for the chosen motor phase :
♦
U or M1 :
90°
♦
V or M2 :
210° ( -150° )
♦
W or M3 : 330° ( -30° )
If not, apply a compensation using the ELEC POS OFFSET parameter. If necessary, repeat steps 6 and 7 until an error of only 1° to 5° is
achieved.
Summary of Contents for AC890PX Series
Page 8: ......
Page 12: ...1 4 C h a p t e r 1 G e t t i n g S t a r t e d AC890PX AC Drive...
Page 17: ...C h a p t e r 2 P r o d u c t O v e r v i e w 2 5 AC890PX AC Drive 890PX bottom wire entry...
Page 22: ...2 10 C h a p t e r 2 P r o d u c t O v e r v i e w AC890PX AC Drive...
Page 74: ...4 8 C h a p t e r 4 A s s o c i a t e d E q u i p m e n t AC890PX AC Drive...
Page 96: ...5 22 C h a p t e r 5 O p e r a t i n g t h e D r i v e AC890PX AC Drive...
Page 162: ...8 22 C h a p t e r 8 T r i p s F a u l t F i n d i n g AC890PX AC Drive...
Page 170: ...9 8 C h a p t e r 9 R o u t i n e M a i n t e n a n c e R e p a i r AC890PX AC Drive...
Page 286: ...D 84 A p p e n d i x D P r o g r a m m i n g AC890PX AC Drive Functional Description...