C h a p t e r 5 : O p e r a t i n g t h e D r i v e
5-13
AC890PX AC Drive
The Trip Condition
When a trip condition is detected, a similar stopping method to NOT COAST STOP is used. The power stack cannot be re-
enabled until the trip condition has been cleared and successfully reset.
Refer to Chapter 8: “Trips and Fault Finding” for further details.
Logic Stopping
The drive can be stopped by setting the NOT STOP to FALSE for a short time, (>100 ms). The stop sequence continues even
if the NOT STOP signal goes inactive before the drive is stopped. Various combinations of stop logic are shown below.
SPEED DEMAND
REMOTE SETPOINT
Speed 0%
RUN FORWARD
NOT STOP
REMOTE SETPOINT
RUN REVERSE
RUN FORWARD ignored
as already running
RUN FORWARD not
ignored as now stopping
RUN FORWARD not
ignored as now stopping
Figure 3.9
Interaction between RUN FORWARD, RUN REVERSE and NOT STOP Parameters
Summary of Contents for AC890PX Series
Page 8: ......
Page 12: ...1 4 C h a p t e r 1 G e t t i n g S t a r t e d AC890PX AC Drive...
Page 17: ...C h a p t e r 2 P r o d u c t O v e r v i e w 2 5 AC890PX AC Drive 890PX bottom wire entry...
Page 22: ...2 10 C h a p t e r 2 P r o d u c t O v e r v i e w AC890PX AC Drive...
Page 74: ...4 8 C h a p t e r 4 A s s o c i a t e d E q u i p m e n t AC890PX AC Drive...
Page 96: ...5 22 C h a p t e r 5 O p e r a t i n g t h e D r i v e AC890PX AC Drive...
Page 162: ...8 22 C h a p t e r 8 T r i p s F a u l t F i n d i n g AC890PX AC Drive...
Page 170: ...9 8 C h a p t e r 9 R o u t i n e M a i n t e n a n c e R e p a i r AC890PX AC Drive...
Page 286: ...D 84 A p p e n d i x D P r o g r a m m i n g AC890PX AC Drive Functional Description...