![Parker AC890PX Series Engineering Reference Download Page 364](http://html2.mh-extra.com/html/parker/ac890px-series/ac890px-series_engineering-reference_3836877364.webp)
D-162
A p p e n d i x D : P r o g r a m m i n g
AC890PX AC Drive
Functional Description
The tables below shows the possible parameter values for FIRST TRIP, and the TRIPS HISTORY function block.
The DISABLED WORD 1 , ACTIVE WORD 1 and WARNINGS WORD 1 parameters use a four digit hexadecimal number to identify individual
trips. Each trip has a unique corresponding number as shown below.
Trip Name (MMI)
Value
Mask
User Disable
Auto-restart
NO TRIP
0
0x0000
N/A
N/A
OVERVOLTAGE
1
0x0001
No
Yes
UNDERVOLTAGE
2
0x0002
No
Yes
OVERCURRENT
4
0x0004
No
Yes
HEATSINK
8
0x0008
No
Yes
EXTERNAL TRIP
16
0x0010
No
Yes
INPUT 1 BREAK
32
0x0020
Yes
Yes
INPUT 2 BREAK
64
0x0040
Yes
Yes
MOTOR STALLED
128
0x0080
Yes
Yes
INVERSE TIME
256
0x0100
Yes
Yes
BRAKE RESISTOR
512
0x0200
Yes
Yes
BRAKE SWITCH
1024
0x0400
Yes
Yes
OP STATION
2048
0x0800
Yes
Yes
LOST COMMS
4096
0x1000
Yes
Yes
CONTACTOR FBK
8192
0x2000
Yes
Yes
SPEED FEEDBACK
16384
0x4000
Yes
Yes
AMBIENT TEMP
32768
0x8000
No
Yes
Summary of Contents for AC890PX Series
Page 8: ......
Page 12: ...1 4 C h a p t e r 1 G e t t i n g S t a r t e d AC890PX AC Drive...
Page 17: ...C h a p t e r 2 P r o d u c t O v e r v i e w 2 5 AC890PX AC Drive 890PX bottom wire entry...
Page 22: ...2 10 C h a p t e r 2 P r o d u c t O v e r v i e w AC890PX AC Drive...
Page 74: ...4 8 C h a p t e r 4 A s s o c i a t e d E q u i p m e n t AC890PX AC Drive...
Page 96: ...5 22 C h a p t e r 5 O p e r a t i n g t h e D r i v e AC890PX AC Drive...
Page 162: ...8 22 C h a p t e r 8 T r i p s F a u l t F i n d i n g AC890PX AC Drive...
Page 170: ...9 8 C h a p t e r 9 R o u t i n e M a i n t e n a n c e R e p a i r AC890PX AC Drive...
Page 286: ...D 84 A p p e n d i x D P r o g r a m m i n g AC890PX AC Drive Functional Description...