A p p e n d i x D : P r o g r a m m i n g
D-91
AC890PX AC Drive
OVER SPEED TRIP
SETUP::TRIPS::OVER SPEED TRIP
Designed for SENSORLESS VEC and CLOSED-LOOP VEC Motor Control Modes.
The
over speed trip operates by looking at speed feedback and comparing it against THRESHOLD.
If the feedback exceeds this threshold for a period greater than DELAY, then a trip is triggered. The trip is only active while the drive is operating in
Closed-Loop or Sensorless Vector Control.
Parameter Descriptions
INHIBIT
PREF: 123.01
Default: FALSE
Range: FALSE / TRUE
Set this parameter to TRUE to disable the over speed trip.
THRESHOLD
PREF: 123.02
Default: 150.00 %
Range: 0.00 to 300.00 %
Sets a threshold below which the trip will not operate. The value of THRESHOLD is compared to the value of SPEED FEEDBACK (from the
SPEED LOOP function block).
DELAY
PREF: 123.03
Default: 0.10 %
Range: 0.00 to 10.00 s
Sets the time the trip must be present for before a trip is triggered.
TRIPPED
PREF: 123.04
Default: FALSE
Range: FALSE / TRUE
This is a diagnostic output indicating the current state of the over speed trip.
Summary of Contents for AC890PX Series
Page 8: ......
Page 12: ...1 4 C h a p t e r 1 G e t t i n g S t a r t e d AC890PX AC Drive...
Page 17: ...C h a p t e r 2 P r o d u c t O v e r v i e w 2 5 AC890PX AC Drive 890PX bottom wire entry...
Page 22: ...2 10 C h a p t e r 2 P r o d u c t O v e r v i e w AC890PX AC Drive...
Page 74: ...4 8 C h a p t e r 4 A s s o c i a t e d E q u i p m e n t AC890PX AC Drive...
Page 96: ...5 22 C h a p t e r 5 O p e r a t i n g t h e D r i v e AC890PX AC Drive...
Page 162: ...8 22 C h a p t e r 8 T r i p s F a u l t F i n d i n g AC890PX AC Drive...
Page 170: ...9 8 C h a p t e r 9 R o u t i n e M a i n t e n a n c e R e p a i r AC890PX AC Drive...
Page 286: ...D 84 A p p e n d i x D P r o g r a m m i n g AC890PX AC Drive Functional Description...