D-80
A p p e n d i x D : P r o g r a m m i n g
AC890PX AC Drive
Parameter Descriptions
THERM PROTECTION
PREF: 134.06
Default: FALSE
Range: FALSE / TRUE
Motor’s thermal protection feature.
●
MAX SPEED
PREF: 134.07
Default: 4300
Range: 0 to INT MAX
Set the motor’s maximum mechanical speed (in rpm)
●
MAX CURRENT
PREF: 134.08
Default: 10.60
Range: 0.00 to 1024.00 A
Set the motor’s maximum rms current. This parameter is used to limit the current demand
●
PERM CURRENT
PREF: 134.09
Default: 4.90
Range: 0.00 to 1024.00 A
Set the motor’s permanent rms current. Permanent current at low speed (in Amp rms) or nominal current.
Refer to MOTOR CURRENT % in the FEEDBACKS function block. A value of 100% = PERM CURRENT.
●
PERM TORQUE
PREF: 134.10
Default: 6.40
Range: 0.00 to 30000.00 Nm
Set the motor’s permanent torque.
Refer to TORQUE FEEDBACK in the FEEDBACKS function block. A value of 100% = PERM TORQUE.
LOW SPEED VALUE
PREF: 134.11
Default: 0
Range: 0 to INT MAX rpm
Set the motor’s low speed value (in rpm) below which the current must be reduced.
If this parameter is unknown, value must be set to 0 rpm.
●
POLES
PREF: 134.12
Default: 10
Range: 0 to 400
Set the number of motor poles, e.g. for a 4 pole motor enter "4".
●
BACK EMF
PREF: 134.13
Default: 85.6
Range: 0.0 to 8192.0 V
Set the motor’s Back EMF phase to phase, rms value (Ke, Volts rms per 1000 rpm)
On a standard PMAC motor the following equation may be used to check that the BACK EMF value is approximately correct:
BACK EMF * MAX SPEED < AC Input voltage
●
R
PREF: 134.14
Default: 3.63
Range: 0.00 to 50.00
Ω
Set the motor’s resistance, between phases at 25 °C. This parameter is used within the current loop.
Summary of Contents for AC890PX Series
Page 8: ......
Page 12: ...1 4 C h a p t e r 1 G e t t i n g S t a r t e d AC890PX AC Drive...
Page 17: ...C h a p t e r 2 P r o d u c t O v e r v i e w 2 5 AC890PX AC Drive 890PX bottom wire entry...
Page 22: ...2 10 C h a p t e r 2 P r o d u c t O v e r v i e w AC890PX AC Drive...
Page 74: ...4 8 C h a p t e r 4 A s s o c i a t e d E q u i p m e n t AC890PX AC Drive...
Page 96: ...5 22 C h a p t e r 5 O p e r a t i n g t h e D r i v e AC890PX AC Drive...
Page 162: ...8 22 C h a p t e r 8 T r i p s F a u l t F i n d i n g AC890PX AC Drive...
Page 170: ...9 8 C h a p t e r 9 R o u t i n e M a i n t e n a n c e R e p a i r AC890PX AC Drive...
Page 286: ...D 84 A p p e n d i x D P r o g r a m m i n g AC890PX AC Drive Functional Description...