B-8
A p p e n d i x B : S e q u e n c i n g L o g i c
AC890PX AC Drive
Switch On
Replaces the RUN FWD, RUN REV and LATCHED RUN parameters of the SEQUENCING LOGIC function block. When
Set (=1) is the same as :
RUN FWD
= TRUE
RUN REV
= FALSE
LATCHED RUN
= FALSE
When Cleared (= 0) is the same as :
RUN FWD
= FALSE
RUN REV
= FALSE
LATCHED RUN
= FALSE
(Not) Disable Voltage
ANDed with the NOT COAST STOP parameter of the SEQUENCING LOGIC function block.
When both Set (=1) is the same as:
NOT COAST STOP
= TRUE
When either or both Cleared (= 0) is the same as :
NOT COAST STOP
= FALSE
(Not) Quick Stop
ANDed with the NOT FAST STOP parameter on the SEQUENCING LOGIC function block.
When both Set (=1) is the same as:
NOT FAST STOP
= TRUE
When either or both Cleared (= 0) is the same as :
NOT FAST STOP
= FALSE