D-24
A p p e n d i x D : P r o g r a m m i n g
AC890PX AC Drive
DRIVE CONFIG
SETUP::DRIVE SETUP::DRIVE CONFIG
This block contains general drive set-up parameters and also determines what hardware can be plugged in the A, B and F slots. These parameters
must be set correctly in order for the drive to run correctly.
Parameter Descriptions
DRIVE NAME
PREF: 136.01
Default: 890 DRIVE
Range:
Enter a user name for the drive.
CONTROL MODE
PREF: 136.02
Default: 0
Range: See below
This parameter defines how the drive will control the motor. If PMAC control is required, the motor wizard feature in the 890 DSE Configuration
Tool
MUST
be used to correctly set-up the motor and feedback device parameters. Failure to do so may result in damage to the servo motor.
Enumerated Value
:
CONTROL MODE
0 : VOLTS / Hz
1 : SENSORLESS VEC
2 : CLOSED-LOOP VEC
3 : 4-Q REGEN
4 : PMAC
Used to control Permanent-Magnet AC brushless motors.
SUPPLY VOLTAGE
PREF: 136.19
Default: 380V to 460V
Range
:
See below
Changes the dynamic braking threshold on expected supply voltage range.
Enumerated Value : Control Mode
0 : 230V
1 : 380V to 480V
2 : 500V
3 : 575V
4 : 690V
Summary of Contents for AC890PX Series
Page 8: ......
Page 12: ...1 4 C h a p t e r 1 G e t t i n g S t a r t e d AC890PX AC Drive...
Page 17: ...C h a p t e r 2 P r o d u c t O v e r v i e w 2 5 AC890PX AC Drive 890PX bottom wire entry...
Page 22: ...2 10 C h a p t e r 2 P r o d u c t O v e r v i e w AC890PX AC Drive...
Page 74: ...4 8 C h a p t e r 4 A s s o c i a t e d E q u i p m e n t AC890PX AC Drive...
Page 96: ...5 22 C h a p t e r 5 O p e r a t i n g t h e D r i v e AC890PX AC Drive...
Page 162: ...8 22 C h a p t e r 8 T r i p s F a u l t F i n d i n g AC890PX AC Drive...
Page 170: ...9 8 C h a p t e r 9 R o u t i n e M a i n t e n a n c e R e p a i r AC890PX AC Drive...
Page 286: ...D 84 A p p e n d i x D P r o g r a m m i n g AC890PX AC Drive Functional Description...