Parallel I/O connection
134
ZW User's Manual
6-1 Parallel I/O connection
I/O Signal Functions
The following describes the functions of I/O signals.
20-pole terminal block
Analog output
Judgment output
ALARM output
BUSY output
ENABLE output
ZERO input
Name
Description
Analog voltage output
This outputs the measured value from -10 V to +10 V as the voltage value.
When measurement not possible: Approx. 10.8V (default value, can be selected by user)
At alarm: Approx. 10.8V
Analog current output
This outputs the measured value, from 4 mA to 20 mA as the current value.
When measurement not possible: Approx. 21 mA (default value, can be selected by user)
At alarm: Approx. 21 mA
Name
Description
HIGH output
Judgment result HIGH (HIGH threshold value < measured value) is output.
PASS Output
Judgment result PASS (LOW threshold value
measured value
HIGH threshold value) is
output.
LOW output
Judgment result LOW (LOW threshold value > measured value) is output.
Name
Description
ALARM output
This turns ON when there is a system error.
Name
Description
BUSY output
This turns ON during sampling with the hold function enabled.
It allows you to check whether or not the self-trigger is functioning correctly.
It also turns ON during bank switching.
Name
Description
ENABLE output
This turns ON when the sensor is ready for measurement.
This output is interlocked with the ENABLE indicator.
Name
Description
ZERO input
This is used to execute and clear a zero reset.
Summary of Contents for ZW-C1*T
Page 70: ...Operating with Sensor Controller 68 ZW User s Manual MEMO ...
Page 116: ...Setting the System 114 ZW User s Manual MEMO ...
Page 134: ...Controll input signal with PC tool 132 ZW User s Manual MEMO ...
Page 209: ...8 Troubleshooting Troubleshooting 8 1 Error Messages 208 8 2 Troubleshooting 210 ...
Page 319: ...Index ZW User s Manual 317 Index 11 ...
Page 321: ......