Appendix I: Parameter blocks
130
W-4510 Weigh Scale Technical Reference Manual
Table 25: Screen 520 OR 521 Frequency input block
Item#
Parameter Name
Parameter Description
0
SIGNAL TYPE
0=off, 1=type 1 input, 2=type 2 input, 3=type 1 test mode, 4=type 2 test
mode
Type 1, counts are inversely proportional to process variable
Type 2, counts directly proportional to process variable
1
Status Location
Shows countdown for timed calibrations
2
SPARE LOCATION
3
SPARE LOCATION
4
TEMPERATURE
COMPENSATION
CHANNEL POINTER
Base address of temp. comp. channel block
5
TACH/FLOWMETER
CHANNEL POINTER
Base address of tach or flow channel block
6
RAW COUNTS
Counts per second from counter
7
AMPLIFIED RAW COUNTS
Location 6 multiplied by location 29
8
DECAY COMPENSATED
COUNTS
Source decay comp. using decay factor at location 27
9
STANDARDIZE
COMPENSATED COUNTS
Compensation per current standardize counts at location 25
10
NORMALIZED COUNTS
Counts input converted to 0–10,000 count range
11
PRODUCT
Linearized and converted to process units, e.g., SGU, lbs/ft, etc
12
FILTERED PRODUCT
Filtered per time constant in product code table
13
TEMPERATURE
COMPENSATED
PRODUCT
Compensated to reference temperature using process temperature and
temperature coefficient
14
FINAL PRODUCT
Final customer process units for display
15
DRY SOLIDS
For slurries only, 0 for all others
16
RATE
Weight per unit time when tach/flow channel enabled
17
PRODUCT MULTIPLIER
18
PRODUCT DIVIDER
(Product Multiplier/Divider)—On slurries (type 2 density measurements)
used as a scale factor for DRY SOLIDS. Used as scale factor to get
FINAL PRODUCT on all other applications
19
RATE MULTIPLIER
Scaling for rate customer units
20
RATE DIVIDER
Scaling for rate customer units
21
REFERENCE
TEMPERATUREX
For temperature compensation
22
MEASUREMENT CUTOFF
SETPOINT
Standardize compensated counts where measurement cuts off
23
CUTOFF TIME CONSTANT
XXXXX seconds for cutoff filtering
24
CUTOFF FLAG
1 if measurement is cut off, 0 if not
25
STANDARDIZE AVERAGE
COUNTS
From last standardize—standardize gain=location 26/location 25
26
CAL. LOW AVG. COUNTS
Starting counts from original calibration
27
DECAY FACTOR
Decay gain=65536/65536—decay factor
28
DECAY REFERENCE
Source type code for decay rate
29
RAW GAIN
Entry=gain factor for location 7
30
FUNCTION CODE
Enter 0 to 9 for selected function code
31
START/[STOP]
Enter 1 to Start a selected function. Enter second 1 to Stop function in
Start/Stop mode. Location zeroes automatically
Summary of Contents for W-4510
Page 9: ...Preface viii W 4510 Weigh Scale Technical Reference Manual Notes...
Page 15: ...Preface xiv W 4510 Weigh Scale Technical Reference Manual Notes...
Page 17: ...Preface xvi W 4510 Weigh Scale Technical Reference Manual Notes...
Page 29: ...Introduction 12 W 4510 Weigh Scale Technical Reference Manual Notes...
Page 125: ...Calibration 108 W 4510 Weigh Scale Technical Reference Manual Notes...
Page 145: ...Diagnostics and repair 128 W 4510 Weigh Scale Technical Reference Manual Notes...
Page 155: ...Appendix I Parameter blocks 138 W 4510 Weigh Scale Technical Reference Manual Notes...