Setup
56
W-4510 Weigh Scale Technical Reference Manual
Procedure 11:Setup gauge span—Channel #2
1. From
the
MAIN MENU 1 OF 2
screen, press SELECT to choose
CALIBRATE
SYSTEM
and press ENTER
2. From
018 CAL MENU 1 OF 2
screen, select
SET PRODUCT CODE
and press
ENTER
3. From
003 PRODUCT CODE SELECTION SCREEN
, type
9
and press ENTER
4.
Return to the
MAIN MENU 2 OF 2
by pressing PREVIOUS SCREEN and NEXT
SCREEN
5. From
MAIN MENU 2 OF 2
, select
SETUP GAGE
and press ENTER
6. Screen
014 SETUP 1 OF 4
displays, press NEXT SCREEN
7. From
014 SETUP 2 OF 4
screen, press SELECT to choose
SET GAGE MEAS
SPAN
and press ENTER
8. From
098 SET GAGE SPAN
screen, select
SET MINIMUM READING
and press
ENTER
9. From
096 MIN SPAN SETTING
screen press HELP
Screen
799
displays “CHANGING SPAN LIMITS REQUIRES GAGE
RECALIBRATION. PRESS HELP.” Press HELP to return to screen
096
and press
ENTER
10. From
096 MIN SPAN SETTING
screen, press select and type in the new minimum
span setting
Press ENTER
11. Press
PREVIOUS SCREEN
to return to screen 098
12. From
098 SET GAGE SPAN
screen, select
SET MAXIMUM READING
and press
ENTER
13. From
097 MAXSPAN SETTING
screen, press select to get to the
NEW SETTING
area and type in the new max span setting
Press ENTER
14.
Connect the write protect jumper JP17
15.
Save to EEPROM
Continued on next page
Summary of Contents for W-4510
Page 9: ...Preface viii W 4510 Weigh Scale Technical Reference Manual Notes...
Page 15: ...Preface xiv W 4510 Weigh Scale Technical Reference Manual Notes...
Page 17: ...Preface xvi W 4510 Weigh Scale Technical Reference Manual Notes...
Page 29: ...Introduction 12 W 4510 Weigh Scale Technical Reference Manual Notes...
Page 125: ...Calibration 108 W 4510 Weigh Scale Technical Reference Manual Notes...
Page 145: ...Diagnostics and repair 128 W 4510 Weigh Scale Technical Reference Manual Notes...
Page 155: ...Appendix I Parameter blocks 138 W 4510 Weigh Scale Technical Reference Manual Notes...