Appendix I: Parameter blocks
W-4510 Weigh Scale Technical Reference Manual
137
Screen 528 Linearizer Block
528 LINEAR CURVES \n
ITEM 000 NEXT=000
CURRENT VAL
NEW VAL
00000
00000
Figure 69: Linearizer curve screen
The base address for screen 528 LINEAR CURVES is 529, item 512.
The
n
on the top line is a number from 0 to 9. This number is the current linearizer curve that
you are accessing. The value of
n
can be incremented by pressing the HELP key.
Table 32: Screen 528 Linearizer block
Item#
Parameter Name
Parameter description
0
CURVE
Start of 40-slope linearizer curve. Uses 41 locations. Curve in normalized units,
usually 0 to 10,000. (i.e., 0–100%)
1
The percent of process span that corresponds to 2.5% of the count range
2
The percent of process span that corresponds to 5.0% of the count range
…
40
HIGH END POINT
OF CURVE
41
CURVE STATUS
0=no curve data entered, 1=40 point curve entered- 41 locations
42
LOW PRODUCT
VALUE
Value of low end of curve in product units. These are Ohmart product units for
calibration
43
HIGH PRODUCT
VALUE
Value of high end of curve in product units for calibration purposes
44
SPARE
45
SPARE
46
SPARE
47
SPARE
48
SPARE
49
SPARE
Summary of Contents for W-4510
Page 9: ...Preface viii W 4510 Weigh Scale Technical Reference Manual Notes...
Page 15: ...Preface xiv W 4510 Weigh Scale Technical Reference Manual Notes...
Page 17: ...Preface xvi W 4510 Weigh Scale Technical Reference Manual Notes...
Page 29: ...Introduction 12 W 4510 Weigh Scale Technical Reference Manual Notes...
Page 125: ...Calibration 108 W 4510 Weigh Scale Technical Reference Manual Notes...
Page 145: ...Diagnostics and repair 128 W 4510 Weigh Scale Technical Reference Manual Notes...
Page 155: ...Appendix I Parameter blocks 138 W 4510 Weigh Scale Technical Reference Manual Notes...