Calibration
100
W-4510 Weigh Scale Technical Reference Manual
Calibrate zero—low on process Channel #2
Before starting this procedure:
5
Have the process at zero
5
Have the actual process value for the empty belt
Procedure 34: Collect data for zero Channel#2—low on process
1.
For the zero, stop the belt.
2. From
the
MAIN MENU 1 OF 2
screen, press SELECT to choose
CALIBRATE
SYSTEM
and press ENTER
3. From
018 CAL MENU 1 OF 2
screen, press SELECT to choose
CALIBRATE
GAGE
and press ENTER
4. From
008 CALIBRATE GAGE
screen, press ENTER at
SELECT CHANNEL
Note: Verify that you are using the correct product code (0-8 for Channel #1 or 9
for Channel #2)
5. From
146 CAL CHANNELS
screen, select
CAL CHANNEL #2
and press ENTER
6. From
185 CAL CHANNEL #2
screen, select
CAL LOW ON PROCESS
and press
ENTER
7. From
187 CALIBRATE LOW ON PROCESS
screen, press SELECT to choose
either
YES
or
NO (ABORT)
8. From
188 CAL TIME LEFT
, press ENTER when the countdown reaches 0
9. From
191 ENTER PROD VAL
screen, enter the actual value of the process and
press ENTER. Screen
191
displays again with the cursor on the
YES
line. Press
ENTER to continue
10. On
the
157
SAVE CALIBRATE RESULT IN UPPER RAM?
screen, press ENTER
on the
YES
line to save to upper RAM or
NO
to abort the save
11.
If you choose to save the results, the AVG. COUNT stores in memory for later use.
Do this only when you are sure the results are correct and you are ready to
continue
12.
Press SELECT to choose the
YES
and press ENTER to continue
13.
Connect the write protect jumper, JP17 and save to EEPROM
14.
Disconnect the write protect jumper, JP17.
Summary of Contents for W-4510
Page 9: ...Preface viii W 4510 Weigh Scale Technical Reference Manual Notes...
Page 15: ...Preface xiv W 4510 Weigh Scale Technical Reference Manual Notes...
Page 17: ...Preface xvi W 4510 Weigh Scale Technical Reference Manual Notes...
Page 29: ...Introduction 12 W 4510 Weigh Scale Technical Reference Manual Notes...
Page 125: ...Calibration 108 W 4510 Weigh Scale Technical Reference Manual Notes...
Page 145: ...Diagnostics and repair 128 W 4510 Weigh Scale Technical Reference Manual Notes...
Page 155: ...Appendix I Parameter blocks 138 W 4510 Weigh Scale Technical Reference Manual Notes...