Engine Heater
This function is used to control the temperature of the engine. A sensor measuring the
cooling water temperature is used to activate an external heating system to keep the
engine at a minimum temperature.
The setpoints adjusted in parameter 6320–6324, 6330 are:
Parameter 6321 setpoint
This se/- the hysteresis is the start and stop points
for the engine heater.
Output A
The relay output for the engine heater.
Input type
Multi-input to be used for temperature measurement.
Hysteresis
This decides how big a deviation from the setpoint is
needed to activate/deactivate the engine heater
Enables
Enables the engine heater function.
Principle Diagram
:
NOTE:
The engine heater function is only active when the engine
is stopped.
Engine Heater Alarm
If the temperature keeps dropping after the start setpoint has been exceeded, an alarm
will be raised if configured in parameter 6330.
Summary of Contents for EMS-GC10
Page 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Page 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Page 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Page 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Page 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Page 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Page 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Page 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Page 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Page 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Page 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Page 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Page 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Page 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...