Section 75
00-02-0878
2013-03-07
- 86 -
Multi-Inputs
The EMS-GC10 unit has three multi-inputs which can be configured to be used as the
following input types:
1. 4-20 mA
2. RMI oil
3. RMI water
4. RMI fuel
5. Binary
NOTE:
The function of the multi-inputs can only be configured in
the PC utility software (USW).
For each input, two alarm levels are available; the parameter numbers of the alarm
settings for each multi-input is controlled by the configured input type as seen in the
following table.
Input Type
Multi-Input 6
Multi-Input 7
Multi-Input 8
4-20 mA
4120/4130
4250/4260
4380/4390
RMI oil
4180/4190
4310/4320
4440/4450
RMI water
4200/4210
4330/4340
4460/4470
RMI fuel
4220/4230
4350/4360
4480/4490
Binary
3400
3410
3420
NOTE:
Only one alarm level is available for the digital input type.
4-20 mA
If one of the multi-inputs has been configured as 4-20 mA, the unit and range of the
measured value corresponding to 4-20 mA can be changed in the PC utility software
(USW) in order to get the correct reading in the display.
RMI (Analog) Inputs
The unit can contain up to three RMI inputs. The inputs have different functions, as the
hardware design allows for several RMI types.
These various types of RMI inputs are available for all multi-inputs:
RMI oil: Oil pressure
RMI water: Cooling water temperature
RMI fuel: Fuel level sensor
For each type of RMI input, it is possible to select between different characteristics
including a configurable one.
Summary of Contents for EMS-GC10
Page 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Page 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Page 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Page 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Page 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Page 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Page 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Page 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Page 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Page 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Page 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Page 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Page 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Page 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...