Section 75
00-02-0878
2013-03-07
- 157 -
MTU MDEC Series - 2000/4000 - Module 302 & 303
Alarm, status and measurement table (read-only) function code 04h.
Addr.
Content
Type
1020
EIC alarms
Bit 0 EIC communication error
Bit 2 EIC shutdown
Bit 3 EIC overspeed
Bit 4 EIC coolant water temperature 1
Bit 5 EIC coolant water temperature 2
Bit 6 EIC oil pressure 1
Bit 7 EIC oil pressure 2
1024
EIC alarms, engine controller
Bit 0 EIC overspeed, shutdown
Bit 1 EIC low oil pressure, warning
Bit 2 EIC low oil pressure, shutdown
Bit 3 EIC low coolant level, shutdown
Bit 4 EIC MDEC ECU failure, shutdown
Bit 5 EIC high coolant temperature, warning
Bit 6 EIC high coolant temperature, shutdown
Bit 7 EIC high intercooler coolant temp, warning
Bit 8 EIC high oil temperature, shutdown
Bit 9 EIC high charge air temperature, shutdown
Bit 10 EIC defect coolant level switch, warning
Bit 11 EIC MDEC yellow alarm, warning
Bit 12 EIC MDEC red alarm, shutdown
Summary of Contents for EMS-GC10
Page 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Page 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Page 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Page 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Page 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Page 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Page 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Page 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Page 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Page 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Page 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Page 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Page 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Page 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...