Section 75
00-02-0878
2013-03-07
- 75 -
Full to Fuel Fill Check
The fuel pump logic includes a Fuel fill check function.
When the fuel pump is running, the fuel level must increase by 2% within the fuel fill
check timer set in parameter 6553. If the fuel level does not increase by 2% within the
adjusted delay time, then the fuel pump relay deactivates and a Fuel Fill Alarm occurs.
NOTE:
The level of increase is fixed at 2% and cannot be changed.
Fail Class
All activated alarms must be configured with a fail class. The fail classes define the
category of the alarms and the subsequent alarm action.
Seven different fail classes can be used. The tables below illustrate the action of each
fail class when the engine is running or stopped.
Summary of Contents for EMS-GC10
Page 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Page 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Page 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Page 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Page 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Page 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Page 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Page 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Page 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Page 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Page 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Page 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Page 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Page 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...