Section 75
00-02-0878
2013-03-07
- 52 -
Analog Tach Feedback
When a magnetic pick-up (MPU) is being used, the specific level of revolutions for
deactivation of the start relay can be adjusted
.
Running Feedback
The diagram below shows how the running feedback is detected at the firing speed
level. The factory setting is 1000 RPM (parameter 6173 Running detect.).
IMPORTANT: Notice that the factory setting of 1000 RPM is
higher than the RPM level of starter motors of typical design.
Adjust this value to a lower value to avoid damage of the
starter motor.
Remove Starter Input
The drawing below shows how the setpoint of the remove starter is detected at the
firing speed level. The factory setting is 400 RPM (parameter 6174 Running detect).
NOTE:
The number of teeth on the flywheel must be adjusted in
parameter 6171 when the MPU input is used.
Summary of Contents for EMS-GC10
Page 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Page 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Page 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Page 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Page 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Page 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Page 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Page 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Page 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Page 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Page 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Page 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Page 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Page 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...