Section 75
00-02-0878
2013-03-07
- 166 -
Operators
Two operators are available, and they can be: “OR” (any operator activates the function
output), “AND” (all activated operators must have status ON to activate the function
output).
Enable the Rule
If this tick box is not ticked, the logic in question will not operate.
Output
This is the selection of the reaction of the system upon activation of the function. Note
that the output has a delay function. If set to 0 s (default), there is no delay.
Commands
Command to the EMS-GC10 unit, for example,, select AUTO running
mode.
Virtual
events
A number of internal (virtual) events that can be activated and used in
another logic line. By using these virtual events, the number of
activating (triggering) events can be expanded from the three
available in each logic line to, in theory, an unlimited number of
events. Virtual events can also be trigged from Modbus.
Relays
Selection of a relay output. The selection of these is option-
dependent.
Inhibits
A selection of inhibit functions for the alarms. Static sync. type:
Selection between static sync. functionalities.
Gov/AVR
control
Possibility to force the speed/voltage control up or down for 5 sec.
Alarm LED
The availability of the alarm LEDs is dependent on the module in
question. There are (4) LED’s mounted on the display front.
EIC
commands
Commands that are related to engine communication.
Buzzer
Incorporated buzzer. Control of activation and deactivation of the
buzzer (e.g., with alarms).
CAN cmd
Command to EMS-GC10 unit connected to the power management
CAN line, f o r e x a m p l e , select AUTO running mode.
Summary of Contents for EMS-GC10
Page 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Page 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Page 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Page 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Page 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Page 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Page 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Page 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Page 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Page 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Page 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Page 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Page 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Page 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...