Section 75
00-02-0878
2013-03-07
- 12 -
Running Modes
The unit has four different running modes and one block mode. The different running
modes are four to three via the display or the PC utility software.
Auto
In auto mode, the unit will operate automatically, and the operator cannot
initiate any sequences manually.
Test
The test sequence will start when the test mode is selected.
Manual
Manual means that the unit will not initiate any sequences automatically,
as is the case with the auto mode. It will only initiate sequences, if
external signals are given.
Block
When the block mode is selected, the unit is not able to initiate any
sequences, for example, the start sequence.
NOTE:
Block mode must be selected when maintenance work is
carried out on the Genset.
NOTE:
The Genset will shut down if block mode is selected while
the Genset is running
NOTE:
If the auto button is pressed twice, the controller will be in
the semi-auto mode. This mode is not supported, and is the same
as the manual mode. Press either the auto or manual button once
to resume normal operation
Alarm and Logs
When an alarm occurs, the alarm is displayed and saved in the Alarm Log.
Press the ESC
button to hide the alarm from the display.
Press the ENTER
button to acknowledge the alarm.
NOTE:
When you acknowledge an alarm, and the alarm condition
is no longer present, the alarm will no longer be displayed in the
Alarm Log.
Press the HORN
button for 2 seconds to view the list of alarms stored in the alarm
log. Press the UP
and Down
Buttons to view the list.
NOTE:
The display will show one alarm at a time.
The alarm log contains both acknowledged and unacknowledged alarms provided that
they are still active (i.e. the alarm condition is still present).
Summary of Contents for EMS-GC10
Page 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Page 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Page 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Page 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Page 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Page 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Page 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Page 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Page 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Page 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Page 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Page 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Page 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Page 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...