Section 75
00-02-0878
2013-03-07
- 39 -
Start Sequence Conditions
The start sequence initiation can be controlled by the following conditions:
•
(oil pressure)
•
(water temperature)
•
(fuel level)
This means that if, for example, the oil pressure is not primed to the sufficient value,
then the crank relay will not engage the starter motor.
The selection is made in parameter 6185. For each of the Analog Input settings, the
rule is that the value (oil pressure, fuel level or water temperature) must exceed the
setpoint of setting 6186 before starting is initiated.
NOTE:
If the value in parameter 6186 is set to 0.0, the start
sequence is initiated as soon as it is requested.
The diagram below shows an example where the analog input signal builds up slowly,
and starting is initiated at the end of the third start attempt.
Summary of Contents for EMS-GC10
Page 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Page 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Page 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Page 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Page 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Page 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Page 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Page 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Page 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Page 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Page 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Page 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Page 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Page 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...