Section 75
00-02-0878
2013-03-07
- 10 -
Display View
Description and Notes
Edit value with the UP
and DOWN
buttons and
save the value by pressing the ENTER
button
NOTE:
The available parameters depend on the set options. Some
parameters can only be changed using the PC utility software
(USW) for EMS-GC10.
Status Line Text
Below is a list of standard conditions with comments.
Condition
Comment
Note
Block
Block mode is activated
Simple Test
Test mode is activated
Full Test
Simple Test ###.#Min
Test mode activated and test timer
counting down
Full Test ###.#Min
Island Man
Genset stopped or running and no
other action taking place
Island Semi
Ready Island Auto
Genset stopped in Auto
Island Active
Genset running in Auto
AMF Man
Genset stopped or running and no
other action taking place (AMF mode)
AMF Semi
Ready AMF Auto
Genset stopped in Auto (AMF mode)
AMF Active
Genset running in Auto (AMF mode)
Load Takeover Man
Genset stopped or running and no
other action taking place (LTO mode)
Load Takeover Semi
Ready LTO Auto
Genset stopped in Auto (LTO mode)
LTO Active
Genset running in Auto (LTO mode)
DG Blocked For
Start
Generator stopped and active
alarm(s) on the generator
GB On Blocked
Generator running, GB open and an
active "Trip GB"
alarm
Shutdown Override
The configurable input is active
Access Lock
The configurable input is activated,
and the operator tries to activate one
of the blocked keys
Summary of Contents for EMS-GC10
Page 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Page 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Page 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Page 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Page 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Page 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Page 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Page 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Page 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Page 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Page 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Page 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Page 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Page 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...