Selections for Alarm Inhibit:
Function
Description
Inhibit 1
M-Logic outputs: Conditions are programmed in M-Logic
Inhibit 2
Inhibit 3
GB ON ( ON)
The generator breaker is closed
GB OFF ( ON)
The generator breaker is open
Run status
Running detected and the timer in parameter 6160 expired
Not run status
Running not detected or the timer in parameter 6160 not expired
Generator voltage > 30%
Generator voltage is above 30% of nominal
Generator voltage < 30%
Generator voltage is below 30% of nominal
MB ON
The mains breaker is closed
MB OFF
The mains breaker is open
NOTE:
The timer in parameter 6160 is not used if binary running
feedback is used.
Summary of Contents for EMS-GC10
Page 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Page 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Page 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Page 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Page 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Page 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Page 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Page 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Page 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Page 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Page 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Page 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Page 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Page 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...