Section 75
00-02-0878
2013-03-07
- 82 -
12. Remote MB ON
The mains breaker ON sequence will be initiated.
13. Remote MB OFF
The mains breaker OFF sequence will be initiated.
14. Remote alarm acknowledge
Acknowledges all present alarms, and the alarm LED on the display stops flashing.
15. Auto start/stop
The genset will start when this input is activated. The genset will be stopped if the input
is deactivated. The input can be used when the unit is in island operation, load takeover
and the AUTO running mode is selected.
16. Remove starter
The start sequence is deactivated. This means the start relay deactivates, and the
starter motor will disengage.
17. Generator breaker closed feedback (GB position ON)
The input function is used as an indication of the generator breaker position. The unit
requires this feedback when the breaker is closed or a position failure alarm occurs.
18. Generator breaker open feedback (GB position OFF)
The input function is used as an indication of the generator breaker position. The unit
requires this feedback when the breaker is opened or a position failure alarm occurs.
19. Mains breaker closed feedback (MB position ON)
The input function is used as an indication of the mains breaker position. The unit
requires this feedback when the breaker is closed or a position failure alarm occurs.
20. Mains breaker open feedback (MB position OFF)
The input function is used as an indication of the mains breaker position. The unit
requires this feedback when the breaker is opened or a position failure alarm occurs.
21. Emergency stop
The input shuts down the engine immediately. At the same time it opens the generator
breaker.
NOTE:
The shutdown fail class must be selected.
22. Low speed
Keeps the genset running at a low RPM.
NOTE:
The governor must be prepared for this function.
Summary of Contents for EMS-GC10
Page 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Page 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Page 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Page 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Page 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Page 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Page 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Page 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Page 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Page 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Page 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Page 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Page 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Page 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...