Section 75
00-02-0878
2013-03-07
- 143 -
Diagnostic Codes
To interpret an SPN and/or FMI number, refer to the documentation of the engine
manufacturer.
SPN means "Suspect Parameter Number", for example, if the coolant water temperature
becomes too high, the SPN code "110" will be shown.
FMI means "Failure Mode Indicator", for example, if the temperature in the above example is
at shutdown level, the FMI code "0" will be shown.
Oc means "occurrence counter" and it indicates how many times a specific alarm has
occurred., for example, if the specific alarm in the above example (SPN 100, FMI 0) has
occurred 2 times, the oc code "2" will be shown.
NOTE:
In the table below a specific SPN number is linked to the same
FMI and oc number.
Active Diagnostic Code (DM1/SPN)
Addr.
Content
Description
1370
SPN diagnostic no. 1
Lo word
1371
SPN diagnostic no. 2
Lo word
1372
SPN diagnostic no. 3
Lo word
1373
SPN diagnostic no. 4
Lo word
1374
SPN diagnostic no. 5
Lo word
1375
SPN diagnostic no. 6
Lo word
1376
SPN diagnostic no. 7
Lo word
1377
SPN diagnostic no. 8
Lo word
1378
SPN diagnostic no. 9
Lo word
1379
SPN diagnostic no. 10
Lo word
1380
SPN diagnostic no. 1
Hi word
1381
SPN diagnostic no. 2
Hi word
1382
SPN diagnostic no. 3
Hi word
1383
SPN diagnostic no. 4
Hi word
1384
SPN diagnostic no. 5
Hi word
1385
SPN diagnostic no. 6
Hi word
1386
SPN diagnostic no. 7
Hi word
1387
SPN diagnostic no. 8
Hi word
1388
SPN diagnostic no. 9
Hi word
1389
SPN diagnostic no. 10
Hi word
1390-1401
Not used
Reserved
Summary of Contents for EMS-GC10
Page 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Page 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Page 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Page 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Page 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Page 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Page 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Page 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Page 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Page 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Page 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Page 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Page 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Page 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...