Section 75
00-02-0878
2013-03-07
- 81 -
Functional Description—Input
1.
Shutdown override
This input deactivates all protections except the over speed protection and the
emergency stop input. The number of start attempts is seven by default, but it can be
configured in parameter 6201. Also a special cool down timer is used in the stop
sequence after an activation of this input.
2. Access lock
Activating the access lock input deactivates the control display push-buttons. It will only
be possible to view measurements, alarms and the log.
3. Binary running detection
The input is used as a running indication of the engine. When the input is activated, the
start relay is deactivated.
4. Remote start
This input initiates the start sequence of the genset when semi-auto or manual mode is
selected.
5. Remote stop
This input initiates the stop sequence of the genset when semi-auto or manual mode is
selected. The genset will stop without cooling down.
6. Test
Changes the present running mode to test.
7. Auto
Changes the present running mode to auto.
8. Manual
Changes the present running mode to manual.
9. Block
Changes the present running mode to block.
NOTE:
When block mode is selected, the running mode cannot be
changed by activating the digital inputs.
10. Remote GB ON
The generator breaker ON sequence will be initiated and the breaker will close if the
mains breaker is opened.
11. Remote GB OFF
The generator breaker OFF sequence will be initiated.
Summary of Contents for EMS-GC10
Page 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Page 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Page 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Page 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Page 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Page 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Page 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Page 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Page 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Page 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Page 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Page 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Page 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Page 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...