Section 75
00-02-0878
2013-03-07
- 18 -
Applications
Applications and Genset Modes
NOTE:
This section about applications is to be used for reference
using the particular Genset mode as starting point. It is not suitable
for reading from beginning to end.
The unit can be used for the applications listed in the table below.
Application
Engine Control
Automatic Mains Failure (no back sync.)
Island operation
Load takeover
Genset mode
Running mode
Auto
Semi
Test
Man
Block
Engine Controller
X
X
X
X
Automatic Mains Failure (no back sync.)
X
X
X
X
X
Island operation
X
X
X
X
Load takeover
X
X
X
X
X
NOTE:
For a general description of the available running modes,
please refer to the chapter "Running mode description".
AMF (No Back Synchronization)
Auto Mode Description:
The unit automatically starts the genset and switches to generator supply at a mains
failure after an adjustable delay time. It is possible to adjust the unit to change to genset
operation in two different ways:
1. The mains breaker will be opened at genset start-up.
2. The mains breaker will remain closed until the genset is running, and
the genset voltage and frequency is OK.
In both cases, the generator breaker will be closed when the generator voltage and
frequency is OK, and the mains breaker is open.
Summary of Contents for EMS-GC10
Page 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Page 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Page 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Page 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Page 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Page 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Page 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Page 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Page 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Page 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Page 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Page 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Page 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Page 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...