Running Output
Parameter 6160 Run status can be adjusted to give a digital output when the genset is
running.
Example of the USW parameter 6160 setup window.
Select the correct relay number in output A and output B and enable the function.
Change the relay function to limit in the I/O menu. Then the relay will activate, but no
alarm will appear.
Example of the USW parameter 5010 setup window.
NOTE:
If the relay function is not changed to "limit" function, an
alarm will appear at every running situation.