Section 75
00-02-0878
2013-03-07
- 41 -
Running feedback
Oil pressure setpoint (parameter 6175).
Running feedback
EIC (engine communication).
Emergency stop
Alarm
Alarms with shutdown" or "trip and stop" fail class.
Stop push-button on display
Manual mode.
Modbus stop command
Manual mode.
Binary stop input
Manual mode.
Deactivate the "auto start/stop"
Auto mode in the following genset modes: Island operation or load
takeover mode.
NOTE:
If the MPU input is to be used to remove the starter, it has
to be set up in parameters 6171, 6172, 6173, 6174.
Parameter Setpoints Related To The Start Sequence:
- Crank failure alarm (parameter 4530 Crank failure)
If MPU is chosen as the primary running feedback, this alarm will be raised if the
specified rpm is not reached before the delay has expired.
- Run feedback failure (parameter 4540 Run feedback fail)
If running is detected on the frequency (secondary), but the primary running feedback,
for example, digital input, has not detected running, this alarm will be raised. The delay
to be set is the time from the secondary running detection and until the alarm is raised.
- Hz/V failure (parameter 4560 Hz/V failure)
If the frequency and voltage are not within the limits set in parameters 2110, 2111,
2112 after the running feedback is received, this alarm is raised when the delay has
expired.
- Start failure alarm (parameter 4570 Start failure)
The start failure alarm occurs, if the genset has not started after the number of start
attempts set in parameter 6190.
- Start prepare (parameters 6180, 6181, 6182, 6183, 6184, 6185, 6186 Starter)
Normal prepare: the start prepare timer can be used for start preparation purposes, for
example, pre-lubrication or pre-glowing (glowing before start). The start prepare relay is
activated when the start sequence is initiated and deactivated when the start relay is
activated. If the timer is set to 0.0 s, the start prepare function is deactivated.
Extended prepare: the extended prepare will activate the start prepare relay when the
start sequence is initiated and keep it activated when the start relay activates until the
specified time has expired. If the extended prepare time exceeds the start ON time, the
start prepare relay is deactivated when the start relay deactivates. If the timer is set to
0.0 s, the extended prepare function is deactivated.
Start ON time: the starter will be activated for this period when cranking. Start OFF
time: the pause between two start attempts.
Summary of Contents for EMS-GC10
Page 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Page 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Page 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Page 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Page 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Page 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Page 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Page 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Page 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Page 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Page 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Page 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Page 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Page 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...