Section 75
00-02-0878
2013-03-07
- 91 -
Scaling Of 4-20 Ma Inputs
The scaling of the analog inputs is made to ensure that the readout of the inputs is
made with a resolution that fits the connected sensor. It is recommended to follow the
guide below when changing the scaling of the analog inputs.
Scaling Example:
1. Use the PC utility software (USW) to configure a multi input to be 4-20mA, in this
example multi input 6 (parameter 10980).
NOTE:
Multi input 7 (parameter 10980) and Multi input 8
(parameter 11000)
2. Read the parameters from the device
3. After reading the parameters the 4-20mA alarm appears under the analog window
pane in the USW. The example below shows how to adjust the analog input alarm. The
three dots to the left of the figures, marked with arrows, are buttons. Adjust the input as
required, for example, 0-5 bar:
Summary of Contents for EMS-GC10
Page 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Page 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Page 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Page 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Page 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Page 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Page 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Page 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Page 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Page 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Page 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Page 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Page 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Page 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...