IPIO quick start
© 2018 Dataprobe Inc.
V180802E
W
hat’s Included
iPIO-xx Unit
Network Cable
Quick Start Guide
A/C Power Supply
Available Online at
dataprobe.com/support-ipio
Complete Product Manual
Device Management Utility
Latest Firmware
Software Developer Tools
Connections
1.
Connect Network.
iPIO
supports 10/100 Ethernet using the cable supplied, or other suitable unshielded twisted pair (Cat
5) cabling. When power is connected to the iPIO, the green Activity LEDs on the network connector indicates when the
network connection is properly established.
2.
Connect Inputs.
(2 Connections per Channel)
Connect the inputs to the iPIO using the screw terminals.
Inputs can be either dry relay or switch contacts, or a +VDC
voltage (3 to 30 V), referenced to a common ground.
Screw terminals are removable for easy installation.
Terminals for each circuit are marked + and G. When
connecting dry relay contacts, the polarity is not significant.
3.
Connect Relays.
(3 Connections per Channel)
Relays are Form C. Connect to the Common (C),
Normally Closed (NC) and Normally Open (NO) as
marked. When the iPIO-8 relay is in the Open Condition,
the Common is connected to the Normally Open. In the
Closed state, the Common and Normally Closed are
connected.
4.
Connect Power.
Each unit is supplied with a n A/C
Power supply. Connect to suitable A/C source, then
power up the iPIO device. The iPIO-2 supports Power
over Ethernet (PoE). Consult the complete manual for more details.
.
Quick Start Guide
The iPIO is Factory set for Dry
Contact Input Only.
Prior to ConnVDC, Jumpers
must be configured.
See full manual or contact Dataprobe
Technical Support.
Relay Specifications
Rating (resistive)
0.5 A 120 VAC or
1 A 24 VDC
Max Carrying Current
2 A
Max Switching Power
60 AV, 24 W
Max Switching Voltage
120 VAC/60 VDC
Max Switching Current
1A
Life Expectancy
5 Million Operations Mech.
100K Oper. at rated load