121
Chapter 3: Maintenance analysis procedures
•
Perform a data collection as part of the removal and
replacement. Refer to
Collect maintenance data
(EFCM Basic
Edition) or
Collect maintenance data
(Element Manager).
NOTE:
Do not remove a power supply unless a replacement part is available.
To avoid product overheating, a removed power supply must be replaced
within five minutes.
Was the maintenance action successful?
NO
YES
↓
The product is operational.
Exit MAP.
Contact the next level of support.
Exit MAP.
3
As indicated by event code
370
, cooling fan status polling is
temporarily disabled and status values for one or more fans exceed a
set threshold. This indicates possible fan degradation or failure.
Is this event code a recurring problem?
NO
YES
↓
A fan failure is indicated.
Go to
step 2
.
Monitor fan operation or recording of additional failure event codes.
Exit MAP.
4
As indicated by event code
426
, an intermittent synchronous dynamic
random access memory (SDRAM) problem may result in switch
failure.
Is this event code a recurring problem?
NO
YES
↓
A CTP card failure is indicated. Replace the switch.
Exit MAP.
Perform a data collection and contact the next level of support. Refer
to
Collect maintenance data
(EFCM Basic Edition) or
Collect
maintenance data
(Element Manager).
Exit MAP.
Summary of Contents for SAN32M-2
Page 2: ......
Page 10: ...SAN32M 2 Installation and Service Manual xii...
Page 14: ...SAN32M 2 Installation and Service Manual xvi...
Page 42: ...SAN32M 2 Installation and Service Manual 16...
Page 120: ...SAN32M 2 Installation and Service Manual 94...
Page 174: ...SAN32M 2 Installation and Service Manual 148...
Page 236: ...SAN32M 2 Installation and Service Manual 210...
Page 240: ...SAN32M 2 Installation and Service Manual 214...
Page 244: ...SAN32M 2 Installation and Service Manual 218...
Page 290: ...SAN32M 2 Installation and Service Manual 264...
Page 308: ...SAN32M 2 Installation and Service Manual 282...
Page 311: ......
Page 312: ...Printed in USA GC26 7763 01...