178
Configuration Switches
Full-Bus/Split-Bus (Switch 1) Configuration
The disk enclosure’s internal bus connects the disk drives together and to the BCCs. This
bus can be set for two modes of operation: full-bus or split-bus mode. When switch 1 is set
to Full Bus (1), all ten disk can be accessed together on a single SCSI bus. In this mode, one
SCSI channel from the FC60 controller is connected to all ten disk modules through either
BCC (typically BCC A).
Note
In full bus mode, all ten disks can be accessed through either BCC. However,
internally each BCC still manages five disks. This means that if the BCC that is
not connected to a SCSI channel fails, access to its five disks will be lost. Failure
of the BCC that is connected to a SCSI channel will render all ten disks
inaccessible.
When switch 1 is set to 0 (split-bus mode), the disk enclosure is split into two separate
buses with five disks to each bus. In split-bus mode, each bus is controlled by a separate
BCC. BCC A (the top BCC) controls the even drive slots (0, 2, 4, 6, 8) and BCC B (the
bottom BCC) controls the odd bus slots (1, 3, 5, 7, 9). In split-bus mode, two SCSI channels
are connected to the disk enclosure, one to a SCSI connector on BCC A and a second a
SCSI connector on BCC B.
Each slot in the disk enclosure is assigned a SCSI ID. A range of IDs is assigned to the odd
disk slots, and a different range to the even slots (see
Table 25
). The two ID ranges include
Table 24
Disk Enclosure Switches
Switch
Setting
Operation
1 - Full-/Split Bus Mode
1
Full-Bus Mode
0
Split-Bus Mode
2 - Stand-Alone/Array Mode
0
Always set to Off (Array Mode)
3 - Bus Reset on Power Fail
0
Must be set to 0
4 - High/Low Bus Addressing
0
Set to 0 (Low addressing)
5 - Not Used
0
Not used; must be set to 0
Summary of Contents for Surestore Disk Array 12h - And FC60
Page 16: ...16 ...
Page 36: ...36 Array Controller Enclosure Components Figure 9 Controller Enclosure Front View ...
Page 41: ...Array Controller Enclosure Components 41 Product Description Figure 13 Controller Fan Module ...
Page 44: ...44 Array Controller Enclosure Components Figure 15 Power Supply Fan Module ...
Page 68: ...68 Capacity Management Features ...
Page 117: ...Topologies for HP UX 117 Topology and Array Planning Figure 39 High Availability Topology ...
Page 122: ...122 Topologies for HP UX Figure 40 High Availability Distance and Capacity Topology ...
Page 126: ...126 Topologies for HP UX Figure 41 Campus Topology ...
Page 130: ...130 Topologies for HP UX Figure 43 Four Hosts Connected to Cascaded Switches ...
Page 142: ...142 Topologies for Windows NT and Windows 2000 ...
Page 158: ...158 Installing the Disk Array FC60 Figure 54 Enclosure EIA Positions for System E Racks ...
Page 161: ...Installing the Disk Enclosures 161 Installation Figure 56 Disk Enclosure Contents ...
Page 172: ...172 Installing the Controller Figure 62 Controller Enclosure Package Contents ...
Page 174: ...174 Installing the Controller Figure 63 Mounting the Controller Enclosure ...
Page 234: ...234 Adding Disk Enclosures to Increase Capacity ...
Page 274: ...274 Managing the Disk Array Using SAM Unassigned disks selected as hot spares ...
Page 345: ...HP UX Diagnostic Tools 345 5 HP UX DIAGNOSTIC TOOLS Overview 346 Support Tools Manager 347 ...
Page 350: ...350 Support Tools Manager Figure 90 mstm Interface Main Window ...
Page 358: ...358 Support Tools Manager ...
Page 440: ...440 FCC Statements USA Only ...
Page 466: ...466 Index ...