D-18
Appendix D
Field Replaceable Units
Removal and Replacement Procedures
Figure D-3 North American Conversion Kit
Installing the North American conversion kit:
1. Attach the plate to the rear panel using the four Torx screws supplied with the kit.
Make certain that the conversion plate is positioned over the right opening in the rear
panel.
2. Connect the wires as follows:
Input Wiring (line cord):
Connect the BLACK (30A) or BROWN (40A) wire to the L1 terminal.
Connect the WHITE (30A) or BLUE (40A) wire to the L2/N terminal.
Connect the GREEN or GREEN/YELLOW wire to the input ground terminal
marked with the following symbol: