Preface-4
WARNING
Batteries can present a risk of electrical shock and/or burn from
high short circuit current. Observe proper precautions. Do not stack
battery trays on top of each other. Do not allow anything to touch the
battery terminals. Do not pierce battery pack wiring insulation. Do
not allow conductive tools or jewelry to touch battery packs or
battery terminals.
Electrical Safety Considerations
• DO NOT use an extension cord or multiple outlet power strips to provide electrical
power to the unit, or any other computer equipment.
• DO NOT install the unit next to open windows or where uncontrolled environmental
conditions could affect it.
WARNING
To reduce the risk of fire, connect the A3589A PowerTrust UPS North
American unit only to a circuit provided with 50 amperes maximum
branch circuit overcurrent protection in accordance with the
National Electrical Code, ANSI/NFPA 70.
The hardwire (worldwide) version may be connected to a circuit
provided with 63 amperes maximum branch circuit overcurrent
protection in accordance with local codes.
CAUTION
• Do not place magnetic media on the UPS.
• Avoid plugging the unit into a wall outlet controlled by a switch. If the
outlet is controlled by a switch, cover or protect the switch from being
turned off accidentally. The switch will not turn off the PowerTrust UPS;
instead, the PowerTrust UPS will go to battery mode, allowing electrical
current to continue to flow to its outputs until the batteries are discharged.
• During power failure conditions, the PowerTrust output will be nominal
230 volts.
CAUTION
• The PowerTrust UPS should NOT be operated from line stabilizers,
ferro-resonant transformers, or other types of line conditions. AC
waveform distortion caused by these devices may cause unexpected
transfer from line operation to UPS battery operation.
• These units should NOT be operated from non-sinusoidal AC voltage
sources. AC input waveforms having distortion caused by large phase
controlled devices, poor utility power, or poor site power may cause
unexpected transfer from line operation to UPS battery operation.
Summary of Contents for PowerTrust A3589A
Page 7: ...Contents Contents 5 ...
Page 8: ...Contents 6 Contents ...
Page 10: ...Contents 8 Figures ...
Page 12: ...Contents 10 Tables ...
Page 14: ...2 ...
Page 20: ...Preface 8 ...
Page 22: ...Preface 10 ...
Page 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Page 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Page 62: ...1 40 Chapter1 Overview Support Information ...
Page 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Page 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Page 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Page 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Page 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Page 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...