Appendix B
B-3
MPE/iX UPS Monitor Error Messages
Power Status Messages
Power Status Messages
The following messages are displayed on the system console to report PowerTrust power
status conditions.
MESSAGE
UPS LDEV <nnn> reports loss of AC input power. (UPSERR 0033)
CAUSE
The specified PowerTrust unit reported that it detected an input power failure;
there has been an AC power failure somewhere in the power path leading into
the unit. The PowerTrust unit has switched to its battery pack to supply
reserve power.
ACTION
If the power failure is brief (not long enough to exhaust the PowerTrust
battery), no action is needed. Otherwise, determine what is causing the power
loss and restore the power before the PowerTrust battery becomes exhausted.
MESSAGE
UPS LDEV <nnn> reports AC input power "Bypass Mode". (UPSWRN
0035)
CAUSE
The specified PowerTrust unit has been placed into its "AC Power Bypass
Mode" of operation. This should only occur when the PowerTrust unit is being
serviced, and the unit is intended to be put into "Bypass Mode". If this message
occurs during normal system operation, there is probably a hardware problem
in the PowerTrust unit.
ACTION
No action is needed if this message occurs during servicing of the PowerTrust
unit. If this message occurs during normal system operation, replace the faulty
PowerTrust unit.
Summary of Contents for PowerTrust A3589A
Page 7: ...Contents Contents 5 ...
Page 8: ...Contents 6 Contents ...
Page 10: ...Contents 8 Figures ...
Page 12: ...Contents 10 Tables ...
Page 14: ...2 ...
Page 20: ...Preface 8 ...
Page 22: ...Preface 10 ...
Page 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Page 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Page 62: ...1 40 Chapter1 Overview Support Information ...
Page 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Page 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Page 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Page 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Page 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Page 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...