A-36
Appendix A
HP-UX UPS Monitor Error Messages
Log-Only Messages
MESSAGE
ups_mond: UPS <tty special file name> Battery Failure -
requires repair
SEVERITY
Critical. PowerTrust hardware has failed. PowerTrust power output is still on,
but the PowerTrust unit will not be able to protect the system against an AC
power failure, if one occurs.
MEANING
The PowerTrust device configured as <tty special file name> informed the UPS
Monitor that its battery has failed the battery test operation. The PowerTrust
unit can no longer be relied upon to supply battery reserve power in the event
of an AC power failure.
CAUSE
A hardware problem in the battery or battery charger circuitry, or elsewhere in
the PowerTrust unit, has caused the battery to fail to perform normally.
ACTION
Call HP Service.
MESSAGE
ups_mond: UPS <tty special file name> High Battery Voltage -
requires repair
SEVERITY
Critical. PowerTrust hardware has failed. PowerTrust power output is still on,
but the PowerTrust unit will not be able to protect the system against an AC
power failure, if one occurs.
MEANING
The PowerTrust device configured as <tty special file name> informed the UPS
Monitor that the voltage output of its battery is too high. The PowerTrust unit
can no longer be relied upon to supply battery reserve power in the event of an
AC power failure.
CAUSE
A hardware problem in the battery or battery charger circuitry, or elsewhere in
the PowerTrust unit, has caused the battery to fail to perform normally.
ACTION
Call HP Service.
Summary of Contents for PowerTrust A3589A
Page 7: ...Contents Contents 5 ...
Page 8: ...Contents 6 Contents ...
Page 10: ...Contents 8 Figures ...
Page 12: ...Contents 10 Tables ...
Page 14: ...2 ...
Page 20: ...Preface 8 ...
Page 22: ...Preface 10 ...
Page 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Page 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Page 62: ...1 40 Chapter1 Overview Support Information ...
Page 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Page 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Page 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Page 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Page 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Page 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...