MPE/iX UPS Monitor Error Messages
Alarm Status Messages
MESSAGE
UPS LDEV <nnn> reports UPS "Overload" condition. (UPSERR
0198)
CAUSE
The specified PowerTrust unit reported an "Overload" condition. The
equipment being powered by the PowerTrust unit is drawing too much power
from the PowerTrust unit AC output. If the excessive power draw continues,
the PowerTrust unit may reach an "Overload Shutdown" condition.
ACTION
1. Reduce the load on the PowerTrust unit by powering off some
non-critical system component.
2. Check for an improper system hardware installation. Correct the
system installation to reduce the loading on the PowerTrust unit.
3. If the system installation is not the problem, find and replace the
faulty system hardware component that is overloading the
PowerTrust unit.
Summary of Contents for PowerTrust A3589A
Page 7: ...Contents Contents 5 ...
Page 8: ...Contents 6 Contents ...
Page 10: ...Contents 8 Figures ...
Page 12: ...Contents 10 Tables ...
Page 14: ...2 ...
Page 20: ...Preface 8 ...
Page 22: ...Preface 10 ...
Page 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Page 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Page 62: ...1 40 Chapter1 Overview Support Information ...
Page 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Page 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Page 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Page 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Page 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Page 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...