Appendix B
B-7
MPE/iX UPS Monitor Error Messages
Alarm Status Messages
MESSAGE
UPS LDEV <nnn> reports UPS "Overload Shutdown" condition.
(UPSERR 0196)
CAUSE
The specified PowerTrust unit reported an "Overload Shutdown" condition.
Too much power was being drawn from the PowerTrust unit AC output by the
computer equipment being powered from this PowerTrust unit. An improper
system installation has put too much load on the PowerTrust unit, or the
computer equipment being powered may be malfunctioning.
ACTION
1. Reduce the load on the PowerTrust unit by powering off some
non-critical system component.
2. Check for an improper system hardware installation. Correct the
system installation to reduce the loading on the PowerTrust unit.
3. If the system installation is not the problem, find and replace the
faulty system hardware component that is overloading the
PowerTrust unit.
MESSAGE
UPS LDEV <nnn> reports UPS "High Ambient Temperature
Shutdown" condition. (UPSERR 0197)
CAUSE
The specified PowerTrust unit reported a "High Ambient Temperature
Shutdown" condition. The temperature of the PowerTrust unit hardware
became too high to permit safe operation, and the PowerTrust unit turned
itself off to prevent equipment damage. The computer room temperature is too
high, or there may be a hardware malfunction in the PowerTrust unit.
ACTION
If the computer room has become too warm, take steps to cool the room. If
room temperature is not the problem, then replace the faulty PowerTrust unit.
Summary of Contents for PowerTrust A3589A
Page 7: ...Contents Contents 5 ...
Page 8: ...Contents 6 Contents ...
Page 10: ...Contents 8 Figures ...
Page 12: ...Contents 10 Tables ...
Page 14: ...2 ...
Page 20: ...Preface 8 ...
Page 22: ...Preface 10 ...
Page 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Page 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Page 62: ...1 40 Chapter1 Overview Support Information ...
Page 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Page 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Page 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Page 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Page 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Page 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...