C-6
Appendix C
Configuring the OS for the PowerTrust UPS
Configuring MPE/iX for the PowerTrust UPS
b. Verify that the RS-232 cable is the correct cable. Although the UPS Port appears to
be a standard 9-pin RS-232 connector, it has a non-standard pin out. You must use
one of these RS-232 cables:
5061-2575
DB9 9-pin male/DB9 9-pin female (2.5 meter)
5061-2569
DB9 9-pin male/DB25 25-pin male (2.5 meter)
c. Verify that the value entered in NMMGR for the port corresponds to the physical
port used on the DTC.
d. Verify these
UPS terminal profile
parameters:
• Baud rate
1200
.
• No parity.
• Terminal type
10
.
• First (and only) device class name
HPUPSDEV
.
e. Power-cycle the DTC to force the DCC (Data Comm Configurator) to download the
DTC as the system finishes booting. This is needed to get the baud rate changed
from its DTC-firmware default of 9600 baud to the NMMGR configured 1200 baud
value.
f. Call the HP Response Center if none of the above resolves the problem.
Summary of Contents for PowerTrust A3589A
Page 7: ...Contents Contents 5 ...
Page 8: ...Contents 6 Contents ...
Page 10: ...Contents 8 Figures ...
Page 12: ...Contents 10 Tables ...
Page 14: ...2 ...
Page 20: ...Preface 8 ...
Page 22: ...Preface 10 ...
Page 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Page 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Page 62: ...1 40 Chapter1 Overview Support Information ...
Page 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Page 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Page 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Page 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Page 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Page 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...