Appendix B
B-11
MPE/iX UPS Monitor Error Messages
Alarm Status Messages
MESSAGE
UPS LDEV <nnn> reports UPS "High Output Voltage Shutdown"
condition. (UPSERR 0203)
CAUSE
The specified PowerTrust unit reported a "High Output Voltage Shutdown"
condition. This is a hardware malfunction within the PowerTrust unit
hardware or possibly in the equipment being powered from the PowerTrust
unit. The PowerTrust unit has shut itself off.
ACTION
Call HP Service.
MESSAGE
UPS LDEV <nnn> reports UPS "Low Output Voltage Shutdown"
condition. (UPSERR 0204)
CAUSE
The specified PowerTrust unit reported a "Low Output Voltage Shutdown"
condition. This is a hardware malfunction within the PowerTrust unit
hardware or possibly in the equipment being powered from the PowerTrust
unit. The PowerTrust unit has shut itself off.
ACTION
Call HP Service.
MESSAGE
UPS Monitor UPS error: Lost communications with UPS LDEV
<nnn>. That UPS is no longer being monitored. (UPSERR 0512)
CAUSE
The UPS Monitor had been monitoring the specified PowerTrust unit LDEV
successfully, then for some reason lost I/O communications with that
PowerTrust unit. The I/O interface cable or I/O interface hardware may have
failed, or the PowerTrust unit itself may have failed.
ACTION
1. Check the specified PowerTrust unit's I/O interface cable and I/O
interface connection at the computer.
2. Check the PowerTrust unit hardware for power connections and
front panel indicators.
NOTE: Even after correcting cable or connection problems, the system must
be rebooted before the software will attempt to resume monitoring the UPS.
Summary of Contents for PowerTrust A3589A
Page 7: ...Contents Contents 5 ...
Page 8: ...Contents 6 Contents ...
Page 10: ...Contents 8 Figures ...
Page 12: ...Contents 10 Tables ...
Page 14: ...2 ...
Page 20: ...Preface 8 ...
Page 22: ...Preface 10 ...
Page 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Page 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Page 62: ...1 40 Chapter1 Overview Support Information ...
Page 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Page 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Page 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Page 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Page 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Page 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...