1-16
Chapter 1
Overview
Control Panel Switches and Indicators
Rear Panel Connectors, Switches, and Indicators (Worldwide
Version)
Figure 1-4 Rear Panel Connectors, Switches, and Indicators (Worldwide
Version)
Connectors and switches on the worldwide version are shown in Figure 1-4 and described
below.
1
Hardwired Output
For the worldwide version, a hole with a strain relief is provided in
the right access panel for making a hardwired output connection
in a manner appropriate to local electrical codes.
Hardwired output is not available with 40A Service Bypass Units.
2
IEC Output
Receptacles
Three IEC320 C19 output receptacles are available on both North
American and worldwide versions of the PowerTrust UPS. Up to
three expansion cabinet Power Distribution Units (PDUs) can be
plugged in here.
3
AC Power Input
For the worldwide (hardwired) version of the PowerTrust UPS, a
hole with a strain relief is provided in the right access panel for
making a hardwired input connection to an AC power source.
Summary of Contents for PowerTrust A3589A
Page 7: ...Contents Contents 5 ...
Page 8: ...Contents 6 Contents ...
Page 10: ...Contents 8 Figures ...
Page 12: ...Contents 10 Tables ...
Page 14: ...2 ...
Page 20: ...Preface 8 ...
Page 22: ...Preface 10 ...
Page 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Page 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Page 62: ...1 40 Chapter1 Overview Support Information ...
Page 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Page 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Page 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Page 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Page 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Page 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...