Installing the UPS
Rackmounting Procedures
Figure 3-8 Battery Precharge Shorting Plate
3. Use a screwdriver to loosen the screw at the center of each thumbscrew, then unscrew
the thumbscrews on either side of the plate and remove it.
4. From the Battery Box, remove the plastic cover marked "REMOVE FOR ASSEMBLY"
and dispose of it.
5. Remove the Battery Box cable.
6. Attach the Battery Box cable connector to the connector on the Electronics Unit.
After you attach the cable, the capacitors will precharge.
7. Check the Precharge Failure LED (see Figure 1-3).
If the LED is off, continue.