Chapter 1
1-29
Overview
Specifications
When the UPS becomes operational, it directs AC line voltage to the output connectors
until the AC input falls out of range. When the AC input is out of range, the UPS
internally generates regulated AC power for up to 15 minutes at rated load and sends it to
the connected equipment through the output connectors.
The UPS should power-on only when the input AC is between 175 V and 264 V, 50/60 Hz.
Other voltage information is shown in the following table.
While running on-line, the output voltage can be from 200 VAC to 244 VAC. While on
battery, the output voltage must be 230 VAC with the output voltage regulated to within
±
3%. Thus, the on-battery output voltage is always in the range of 234 VAC and 223 VAC.
Operating Mode
Output Voltage
On-line
230 +6/-13%
On-battery
230
±
3%
Automatic Bypass
Tracks Input Voltage
Service Bypass
Tracks Input Voltage
Summary of Contents for PowerTrust A3589A
Page 7: ...Contents Contents 5 ...
Page 8: ...Contents 6 Contents ...
Page 10: ...Contents 8 Figures ...
Page 12: ...Contents 10 Tables ...
Page 14: ...2 ...
Page 20: ...Preface 8 ...
Page 22: ...Preface 10 ...
Page 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Page 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Page 62: ...1 40 Chapter1 Overview Support Information ...
Page 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Page 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Page 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Page 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Page 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Page 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...