3-26
Chapter 3
Installing the UPS
Examples of PowerTrust Connections in a System
Example 4: Dual Expansion Cabinet System
(Factory-Integrated)
Figure 3-14 shows a factory-integrated system with two expansion cabinets. Note these
features:
• Only one PDU is installed in each expansion cabinet. Both PDUs receive their power
from the PowerTrust UPS located in the right-hand expansion cabinet. (The 30A
connector supplies the PDU in the left-hand cabinet, and the IEC320 connector supplies
the PDU in the right-hand expansion cabinet.)
• All peripherals and fans in both expansion cabinets are being powered via the single
PDU located within the right-hand cabinet. Powering all expansion cabinet peripherals
in this manner may not be possible in every case due to power loading restrictions.
• The system console is being powered from the single PDU in the left-hand expansion
cabinet.
• The system SPU is being powered from the 30A output of the UPS in the left-hand
cabinet.
Summary of Contents for PowerTrust A3589A
Page 7: ...Contents Contents 5 ...
Page 8: ...Contents 6 Contents ...
Page 10: ...Contents 8 Figures ...
Page 12: ...Contents 10 Tables ...
Page 14: ...2 ...
Page 20: ...Preface 8 ...
Page 22: ...Preface 10 ...
Page 52: ...1 30 Chapter1 Overview Specifications Figure 1 8 UPS Input Voltage Transfer Points ...
Page 56: ...1 34 Chapter1 Overview UPS Modes Figure 1 10 Simplified UPS 5 5 kVA UPS Block Diagram ...
Page 62: ...1 40 Chapter1 Overview Support Information ...
Page 76: ...2 14 Chapter2 Unpacking and Inspecting Shipping and Storage Requirements ...
Page 104: ...3 28 Chapter3 Installing the UPS Examples of PowerTrust Connections in a System ...
Page 116: ...5 4 Chapter5 Verification Procedures Load Testing ...
Page 148: ...7 6 Chapter7 Cleaning and Maintenance Exchanging Batteries Fan ...
Page 190: ...A 42 AppendixA HP UX UPS Monitor Error Messages Log Only Messages ...
Page 218: ...C 8 AppendixC Configuring the OS for the PowerTrust UPS Power Failing the UPS ...