4-8
Chapter 4
Power-On/Power-Off Procedures
Charging the Batteries
Charging the Batteries
The 5.5 kVA PowerTrust UPS's batteries must be charged before the UPS can provide
battery generated output AC power in the event of an input power failure. For the
batteries to charge, input AC power must be present, the UPS/BATTERY switch must be
in the
ENABLE
position, and the MAIN INPUT breaker must be ON.
Charging the batteries can take up to 14.5 hours for a 90% recharge. The recharge time
may be considerably less if the batteries are not fully discharged.